Raypak Heater Fault Code Guide (2024)

Raypak Heater Fault Code Guide (1)

February 22, 2016 Charlie Ramirez

No one likes to get an error code on any piece of technology, especially on a Raypak heater. It means something is wrong and needs to be addressed soon. The panic really doesn’t set in until you realize error code BD1 means absolutely nothing to you. Error codes are both curses and blessings. Although an error message is never really a good thing, at least it’s an indication of what the problem is. Just imagine how much easier it would be to diagnose diseases if humans came with error codes.)Usually, depending upon the manufacturer, the manufacturer will include a manual detailing what may have triggered the error message and possible solutions to fix the issue. All error code guides are not made equal.

Still, even if the error codes were listed in the manual, what are the odds you know where that manual is? Unless you’re like my mom whokeeps all her paperwork in afiling cabinet, the manual was probably tossed a week after your product was working properly. Heaters, though, can be rather tricky without the manual. I love the saying, “hindsight is 20/20,” because it’s so true. How many times did you wish you kept something after you have convincedyourself that you didn’t need it and threw it away? Or maybe it’s just me.

Our goal with this blog is to aid you in identifying and defining the error code on your Raypak heater and to provide possible solutions, as per the manufacturer. If we don’t have a solution or do not address your particular issue, it’s always best to contact Raypak directly.

The majority of Raypak heaters will have a digital readout. The digital readout helps pool owners read error codes on the actual heater. The models with digital thermostats are programmed to display a variety of status and diagnostic messages, depending on the operating conditions.Raypak Heater Fault Code Guide (3)

They are also equipped with onboard diagnostic controls. If there is a safety fault, a fault code will be displayed along with a service indication. (see pic on right) The word “SERVICE” will flash on and off if the PC board detects a known issue. The fault code is displayed in 3 big letters in the lower left of the display.

Below is a chart we created to help pool owners identify the meaning of Raypak’s fault code. It also includes possible solutions to fix the issue. Keep in mind, this is not a substitute for the installation and operation manual. Should you need further advice or technical information, please give Raypak a call at 805-278-5300.

Fault Code DisplayDefinitionPossible Solutions
BD1Board failure1. If this code appears and stays on, turn off power to board at toggle switch and source, then re-establish power.
2. If code reappears, replace board as the main processor failed to start.
EEPIndicates that memory failed to start on main processor.1. Turn off power at toggle switch and source, then re-establish power.
2. If code reappears, replace board as memory has failed.
FANIndicates the Pilot was lost, or the air pressure switch is not closed when required. 1. Check for correct incoming power at fan relay- 120V or 240V and at fan motor.
2. If pilot is confirmed, check for 24V minimum out of fan relay to pressure switch.
3. If switch does not make when fan is operating, verify the tuning between fan housing and switch is connected and is not kinked.
4. Soft lock out after 3 attempts- automatically resets after 5 minutes.
FFLIndicates a false flame signal. 1. Check to see if pilot is staying lit after CFH is satisfied. If pilot stays lit, the pilot valve in the gas valve is hanging open. Replace gas valve.
2. If gas valve is working properly, problem lies with the pilot system or board. Turn power off at toggle switch.
3. Unplug ignition wire from board and pilot and remove green ground wire from burning tray. Clean and reconnect ground wire.
4. Turn power on. If no spark at ignition module, turn power off and replace the PC board.
4. If you saw a spark at Ignition Module, turn off the power and reconnect wires.
6. Turn power on and unit should fire.
GVCNo power detected at PV or MV when commanded.1. Turn power OFF and disconnect Ignition Wire and Gas Valve wires from board.
2. Power ON and watch for spark at module.
3. If no spark, turn power OFF, and replace board.
4. If spark is observed, turn off power and reconnect wires. The unit should fire.
5. If unit does not fire and code reappears, power OFF, disconnect valve wires from board and remove MV, PV, and ground wires. Clean and reconnect.
7. If unit does not fire, replace the gas valve.
GVOPower found at either PV or MV at the incorrect time.1. Turn power OFF and disconnect Ignition Wire and Gas Valve wires from board.
2. Power ON and watch for spark at module.
3. If no spark, turn power OFF, and replace board.
4. If spark is observed, turn off power and reconnect wires. The unit should fire.
5. If unit does not fire and code reappears, power OFF, disconnect valve wires from board and remove MV, PV, and ground wires. Clean and reconnect.
7. If unit does not fire, replace the gas valve.
8. Low power to transformer can cause a GVO fault.
HL1The high-limit has exceeded 135F1. Possible excessive water temperature in the tube bundle. Once heater cools, high limits resets automatically.
2. Check for blockage in tubes.
3. Check for low water flow.
4. Check Unitherm governor- replace if necessary
5. check bypass assembly- replace spring or bypass if necessary
HL2The high-limit has exceeded 135F1. Possible excessive water temperature in the tube bundle. Once heater cools, high limits resets automatically.
2. Check for blockage in tubes.
3. Check for low water flow.
4. Check Unitherm governor- replace if necessary
5. check bypass assembly- replace spring or bypass if necessary
IGNIgnition failure1. If the unit fails to hold a flame after 3 attempts, it will go into a hard lockout. Interrupt the power supply to clear the lockout and check for air in the gas line or not enough gas pressure.
2. IGN only appears after pilot has proved and main valve has been powered.
ILOIgnition lockout (Propane units only)1. The heater has performed too many attempts to ignite the main burner and will take a short break.
2. Inspect pilot assembly.
3. If pilot assembly is OK, then the culprit may be your PC board.
PRSLow water pressure1. Check water levels at skimmer face. (should be middle of skimmer face)
2. Ensure pump is running.
3. Check filter pressure. Backwash if necessary.
4. Check heater location- if more than 5 ft above or below water level- adjust pressure switch.
ROLThermal fuse tripped inside heater due to excessive heat or flame roll-out detected.1. Possible downdraft of burner flame. If sensor has red reset button, press button & determine cause.
2. Does your unit need a high wind stack?
3. Check wiring for burns- especially the ground wire and wires at gas valve.
4. Replace wires if necessary.
SNSTemperature sensor is out of acceptable range.1. Water temperature is below 36F or above 110F
2. If the two thermistors are more than 2 degrees apart, the SNS code will appear.
3. Loose or corroded connection at P1.
4. If the sensor is not mounted all the way into the JACO fitting on the header, it may give a false reading.

Raypak Heater Fault Code Guide (2024)

FAQs

How to troubleshoot Raypak pool heater? ›

Go make sure there aren't any tripped circuit breakers in the fuse box, then check that the unit's time clock is set to the “On” position. Check Filters & Strainers: Problems with slow or inefficient heating, as well as overly noisy operation, can sometimes be traced back to dirty filters and strainers.

How to read Raypak serial numbers? ›

The rating plate will be either a gold or silver color with the Raypak logo. The serial number will have 10 digits. The date code is found in the first four digits of the serial number, for example, a unit made in April of 2001 will have the first four digits read as 0104.

What is the CLK code on a Raypak heater? ›

This is what Raypak/Rheem lists as a definition for CLK on the display: "Clock - Time Clock. Heater is off by programmed control of a Time Clock."

What is the PRS code on a Raypak heater? ›

The PRS fault code on a Raypak hot tub this indicates an open pressure switch. The heater is not getting enough water flow to close the pressure switch.

What is the life expectancy of a Raypak pool heater? ›

The average life of a pool heater is between 15 and 25 years with regular usage and proper maintenance, but there are various factors that impact that projection.

How do you read a serial code? ›

The 1st number is the YEAR of manufacture; the 2nd & 3rd numbers indicate the MONTH of manufacture. Please see the detailed explanation and examples provided below.

What can you tell from a serial number? ›

A serial number is a unique identifier assigned to a specific product by the manufacturer. It helps to distinguish one product from another and can be used for warranty purposes or to track inventory.

What does the code if mean on a pool heater? ›

There are different models of Hayward units, some use a spark igniter, some use a glow igniter. Most of the time, the IF code means that the igniter has failed, the gas valve has failed, or on units with flame sensing technology, the flame sensor is dirty and needs to be cleaned with sandpaper.

What is the e1 code on a pool heater? ›

E01 or ERR01

Usually, this code will indicate a flow sensor issue. It could be caused by a lack of water flow through the heater, a malfunctioning flow sensor, or a blockage in the plumbing.

What does HF mean on pool heater? ›

Troubleshooting Hayward Gas Heater Error Codes
CodeDescription
HFFlame present with gas valve “OFF” error
PFElectrical supply wiring error
AOBlower vacuum switch open error
AOBlower vacuum switch open when expected closed error
14 more rows

What does FS mean on a pool heater? ›

FS Indicator. ISSUE. The heat pump has sensed the evaporator coil is icing up. RESOLUTION. ACTIVE DEFROST - Reversing Units.

What does SPK mean on a Raypak pool heater? ›

What does that mean? SPK means that the heaters safeties are all closed. You have to change the set point above the water temperature in the pool or spa so the heater will light the pilot and prove that it is lit.

What is the PF code on a heater? ›

PF code means, Electrical supply wiring error... This code will display if 120V polarity is reversed, low voltage is detected, or if the ground path is not sufficient. Reset is immediate after error is corrected. Have you tried resetting the breaker for the heater to see if the error is cleared?

Why is my pool heater clicking but not igniting? ›

The “clicking,” indicates that the ignitor is sparking and the heater is trying to fire, but the gas and the “spark" are not reaching each other. If the heater has recently been installed, the first thing that must be checked is the gas pressure.

Why is my heat pump running but not heating my pool? ›

Be sure that the water level in the pool is correct, the filter and baskets are clean, and the pump running fully primed, to provide enough water flow to keep the heater pressure switch and/or flow switch in the closed position.

Why is my pool heater not going through the water? ›

A dirty pool filter wins for the most popular water flow issue on a heater service call. Luckily, it's also the easiest one to diagnose and fix. You can overcome this issue by having a pool heater service tech or pool specialist remove the filter and run the pump again without a filter in.

Top Articles
Latest Posts
Article information

Author: Cheryll Lueilwitz

Last Updated:

Views: 5998

Rating: 4.3 / 5 (74 voted)

Reviews: 89% of readers found this page helpful

Author information

Name: Cheryll Lueilwitz

Birthday: 1997-12-23

Address: 4653 O'Kon Hill, Lake Juanstad, AR 65469

Phone: +494124489301

Job: Marketing Representative

Hobby: Reading, Ice skating, Foraging, BASE jumping, Hiking, Skateboarding, Kayaking

Introduction: My name is Cheryll Lueilwitz, I am a sparkling, clean, super, lucky, joyous, outstanding, lucky person who loves writing and wants to share my knowledge and understanding with you.