My heater is doing funny things today. Error code “water sw open”. Google isn’t being much help. Any thoughts are appreciated.

uxbridgechris

0

Bronze Supporter

Jan 25, 2018
655
uxbridge, Ontario Canada
  • May 29, 2020
  • Add bookmark
  • #3

Ya I read that thanks. It’s the first hit in google. The question is answered by an appliance repair guy that just googled possible answers. Lol.
Raypak says “check to make sure there are no obstructions. Clean skimmer and pump basket and filter”. That’s not the issue here. I am clean. water is moving thru the system at 60gpm like always.

uxbridgechris

0

Bronze Supporter

Jan 25, 2018
655
uxbridge, Ontario Canada
  • May 29, 2020
  • Add bookmark
  • #4

The heater sounds like it’s trying to fire. “Spark” is flashing and so is “no demand”. I am not calling for heat.

  • May 29, 2020
  • Add bookmark
  • #5

Ok. I’ve been working on it for the last hour. I unpowered it and powered back on.

if the heater is in “Remote mode”. It will fire up even if my automation isn’t calling for heat. I have even gone so far as to unhook my automation and it still fires up even know there is no call for heat.

Manual mode, it is functioning as normal.

kimkats

Mod Squad

LifeTime Supporter

Jul 10, 2012
54,985
Tallahassee, FL
  • May 29, 2020
  • Add bookmark
  • #6

Make sure to keep notes of what you have done so far and do coming up so we can trace back to what worked.

@ajw22 @jimmythegreek @Pool Clown @bdavis466 or any others that might have input please just in!

ajw22

TFP Expert

Gold Supporter

Silver Supporter

Bronze Supporter

TFP Guide

Jul 21, 2013
55,185
Northern NJ
Pool Size
35000
Surface
Plaster
Chlorine
Salt Water Generator
SWG Type
Pentair Intellichlor IC-60
  • May 29, 2020
  • Add bookmark
  • #7

I am confused. Are you past the "water switch open" problem and the heater is running?

Describe your current problem.

  • “Water sw open”. Raypak 266 digital. (10)

Reactions:

steevo

uxbridgechris

0

Bronze Supporter

Jan 25, 2018
655
uxbridge, Ontario Canada
  • May 29, 2020
  • Add bookmark
  • #8

When I came around the corner to my heater this morning I could hear the electronic ignition trying to start every few seconds. Pump was not running because I had it turned off. The display was alternating “no demand” and “water sw open”.

I unplugged the heater

When I plugged the heater back in, “water sw open” was gone. I turned pump on circulate but made sure heat was off On my controller. The heater kicked into “spark” and fired up even know my controller was not calling for heat. I powered heater off and disconnected the 2 wire connection to the controller. Again, when I powered heater on, it fired up.

I switched heater from “remote” to “manual” and the heater functions as it should. In my opinion when Heater is on “remote” mode, the heater is always acting like there is a call for heat.

ajw22

TFP Expert

Gold Supporter

Silver Supporter

Bronze Supporter

TFP Guide

Jul 21, 2013
55,185
Northern NJ
Pool Size
35000
Surface
Plaster
Chlorine
Salt Water Generator
SWG Type
Pentair Intellichlor IC-60
  • May 29, 2020
  • Add bookmark
  • #9

uxbridgechris said:

When I came around the corner to my heater this morning I could hear the electronic ignition trying to start every few seconds. Pump was not running because I had it turned off. The display was alternating “no demand” and “water sw open”.

That was what would be expected with the pump not running. “water sw open” means there is no water flow which there was not.

uxbridgechris said:

I unplugged the heater

No reason to do that. Just turn on the pump.

uxbridgechris said:

When I plugged the heater back in, “water sw open” was gone. I turned pump on circulate but made sure heat was off On my controller. The heater kicked into “spark” and fired up even know my controller was not calling for heat. I powered heater off and disconnected the 2 wire connection to the controller. Again, when I powered heater on, it fired up.

Where did you disconnect the 2 wire "firemans switch"?

uxbridgechris said:

I switched heater from “remote” to “manual” and the heater functions as it should. In my opinion when Heater is on “remote” mode, the heater is always acting like there is a call for heat.

So that says you need to open up the heater and see what is going on with the 2 wire connection there. It sounds like the 2 wires are shorted in the heater. Maybe a critter got inside and chewed the wire.

uxbridgechris

0

Bronze Supporter

Jan 25, 2018
655
uxbridge, Ontario Canada
  • May 29, 2020
  • Add bookmark
  • #10

alw22. I am 99% sure you solved the problem. The 2 wire from my controller was too short in 2018 when I installed it so I spliced it. I cut the wire before the splice and the problem of it wanting to fire up had stopped. My multimeter is at work but I suspect that splice is bad and maybe a strand is poking thru. Thanks so much. Will follow up when I repair and test. Raining here now.

Enjoying this content?

Support TFP with a donation.

Give Support

ajw22

TFP Expert

Gold Supporter

Silver Supporter

Bronze Supporter

TFP Guide

Jul 21, 2013
55,185
Northern NJ
Pool Size
35000
Surface
Plaster
Chlorine
Salt Water Generator
SWG Type
Pentair Intellichlor IC-60
  • May 29, 2020
  • Add bookmark
  • #11

uxbridgechris said:

alw22. I am 99% sure you solved the problem. The 2 wire from my controller was too short in 2018 when I installed it so I spliced it. I cut the wire before the splice and the problem of it wanting to fire up had stopped. My multimeter is at work but I suspect that splice is bad and maybe a strand is poking thru. Thanks so much. Will follow up when I repair and test. Raining here now.

And now we have "the rest of the story". “Water sw open”. Raypak 266 digital. (15)

uxbridgechris

0

Bronze Supporter

Jan 25, 2018
655
uxbridge, Ontario Canada
  • May 29, 2020
  • Add bookmark
  • #12

Hahha. Ya. There is always a detail that is left out that seems insignificant at the time.....I took great care in that splice. Staggered and soldiered it. Now that I think about it, it probably has water in it. Ouch. I’m going to fix that more carefully. Thanks again so much.

kimkats

Mod Squad

LifeTime Supporter

Jul 10, 2012
54,985
Tallahassee, FL
  • May 29, 2020
  • Add bookmark
  • #13

Allen in for the win AGAIN!!!!!! “Water sw open”. Raypak 266 digital. (18)

ajw22

TFP Expert

Gold Supporter

Silver Supporter

Bronze Supporter

TFP Guide

Jul 21, 2013
55,185
Northern NJ
Pool Size
35000
Surface
Plaster
Chlorine
Salt Water Generator
SWG Type
Pentair Intellichlor IC-60
  • May 29, 2020
  • Add bookmark
  • #14

Get rid of the splice and replace the 2 wire cable. Any 2 wire cable will work.

You must log in or register to reply here.

“Water sw open”. Raypak 266 digital. (2024)

FAQs

Why is my Raypak water heater not turning on? ›

Check the Power: If your Raypak pool heater isn't working at all, the problem could be something as simple as a lack of power. Go make sure there aren't any tripped circuit breakers in the fuse box, then check that the unit's time clock is set to the “On” position.

What does it mean when my pool heater says no demand? ›

No demand means that you have met the desired temperature. If the pool temperature falls 2° below your Set Temperature , then the heater will come back on. Then it will register a heating prompt, letting you know that the heater is back on. Pool and Spa Expert: Patrick D.

What does open water sensor mean on pool heater? ›

The model is inside the pool heater. I do not need the Aqualink model number. Anyways the answer is as I mentioned before. (open water temp sensor) That means the control board can no longer read the temperature of the incoming water.

How do I know if my pool valve is open? ›

In order to tell if the valve is open or closed, the general rule is, if the handle is switched 90deg to the flow, it is off. As you can see from the diagram above, if the handle is in line with the flow path, it is on.

Can a pool heater get clogged? ›

Your pool heater contains a filter that prevents contaminants from circulating through the filter and causing a problem. However, if the filter becomes clogged, it can prevent the correct amount of water from passing through. Without sufficient water pressure, your heater won't be able to work.

Why is my pool heater not getting enough water flow? ›

A dirty pool filter wins for the most popular water flow issue on a heater service call. Luckily, it's also the easiest one to diagnose and fix. You can overcome this issue by having a pool heater service tech or pool specialist remove the filter and run the pump again without a filter in.

How to turn on Raypak pool heater? ›

to start the heater first press the mode button and select pool or spa. Then press the up arrow to set the desired water temperature. Be sure to select a temperature higher then current water temperature and heater will turn on.

Why won t my Raypak propane pool heater ignite? ›

There are several reasons that a pool heater will not light. The most common cause is a fuel delivery issue. In addition, the gas pressure would have to be measured with a manometer to ensure it is within the operating pressures specified in the installation manual.

Can you reset a pool heater? ›

Reset your pool heater by flipping the breaker switch in the electrical panel to “off” and then “on.” Your breaker may be located in a disconnect box near your pool heater or in the breaker panel in your home.

Why is my pool heater not detecting water? ›

Your heater may have inadequate water flow due to a dirty filter, closed valve, external bypass, reversed water connections, or pressure switch out of adjustment. It is also possible that your thermostat is out of calibration or needs to be replaced.

How many hours a day should I run my pool heater? ›

A bigger pool heater may only require two hours to have a pool nice and warm and a smaller heater made need three hours to get that same size swimming pool to a comfortable swim temperature. The type of swimming pool heater a homeowner has will also be a factor in when to run a pool heater.

What would cause a pool heater to not ignite? ›

Tripped circuit breaker: The most common reason for a pool heater not turning on is a tripped circuit breaker or blown fuse. Check your breaker box and reset any tripped breakers or replace any blown fuses. ✓ Low water flow: If there isn't enough water flowing through the heater, it won't turn on as a safety measure.

What is open outlet water heater? ›

For open-outlet (low-pressure) storage type electric water heaters, they are designed to supply only one serving point and the outlet is controlled by a special water mixer which maintains a vented passage for the air inside the tank to the atmosphere.

What does SPK mean on a Raypak pool heater? ›

What does that mean? SPK means that the heaters safeties are all closed. You have to change the set point above the water temperature in the pool or spa so the heater will light the pilot and prove that it is lit.

What does water flow lockout mean on pool heater? ›

And without enough water to distribute heat into, a pool heater can easily overheat and experience permanent damage. If you see the “Water Flow Lockout” notification appear on your Gulfstream's display, or notice the pump shutting down for non-electrical reasons, then chances are poor circulation is to blame.

Top Articles
Latest Posts
Article information

Author: Errol Quitzon

Last Updated:

Views: 6008

Rating: 4.9 / 5 (79 voted)

Reviews: 94% of readers found this page helpful

Author information

Name: Errol Quitzon

Birthday: 1993-04-02

Address: 70604 Haley Lane, Port Weldonside, TN 99233-0942

Phone: +9665282866296

Job: Product Retail Agent

Hobby: Computer programming, Horseback riding, Hooping, Dance, Ice skating, Backpacking, Rafting

Introduction: My name is Errol Quitzon, I am a fair, cute, fancy, clean, attractive, sparkling, kind person who loves writing and wants to share my knowledge and understanding with you.